VFNC3S 3-phase 240V Inverter Toshiba Tosvert
VFNC3S 3-phase 240V Models
VFNC3-2001P : 0.1kW
VFNC3-2002P : 0.2kW
VFNC3-2004P : 0.4kW
VFNC3-2007P : 0.75kW
VFNC3-2015P : 1.5kW
VFNC3-2022P : 2.2kW
VFNC3-2037P : 3.7kW
Specifications
Item | Specification | ||||||||
Input voltage class | 1-phase 120V / 1-phase 240V / 3-phase 240V | ||||||||
Applicable motor (kW) | 0.1 | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | ||
Model | Input voltage class | Type-form | VFNC3/VFNC3S | ||||||
3-phase 240V | VFNC3- | 2001P | 2002P | 2004P | 2007P | 2015P | 2022P | 2037P | |
Rating | Output capacity (kVA) Note 1) | 0.3 | 0.6 | 1.3 | 1.6 | 3.0 | 4.2 | 6.7 | |
Output current(A) Note 2) |
3-phase 240V | 0.7(0.7) | 1.4(1.4) | 2.4(2.4) | 4.2(3.6) | 7.5(7.5) | 10.0(8.5) | 16.7(14.0) | |
Output voltage Note 3) | 3-phase 200 to 240V | ||||||||
Power supply | Voltage-frequency | 3-phase 240V class: 3-phase 200V to 240V – 50/60Hz | |||||||
Allowable fluctuation | 3-phase 240V class: Voltage 170 to 264V Note 4), frequency +/-5% | ||||||||
Feature | Output voltage range | Adjustable within the range of 50 to 330V by correcting the supply voltage (not adjustable above the input voltage) Note 3) | |||||||
Output frequency range | 0.1 to 400Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 400Hz | ||||||||
Voltage / frequency characteristic |
V/f constant mode, variable torque mode, automatic torque boost mode, vector control mode, automatic energy-saving mode. Auto-tuning. | ||||||||
Overload current rating | 150%-60 seconds | ||||||||
Functions | PID control, regenerative power ride-through control, auto-restart control, dynamic deceleration control, frequency UP/DOWN input control, 3-wire control, RS485 communication(2-wire), programmable input/output terminal, voltage/current analogue output, pulse train output, parts replacement alarming signal monitor/output, detailed monitor display at trip, free unit selection, password lock, guidance | ||||||||
Environments | Use environments | Indoor, not exposed to direct sunlight, without corrosive gas, explosive gas, oil mist, dust and dirt etc Altitude: 3000m max.(output current needs to be reduced for altitude above 1000m) Vibration: less than 5.9m/s2 (10 to 55Hz) |
|||||||
Ambient temperature / Relative humidity |
-10 to + 60 degreeC (Above 40 degreeC, remove the protective seal from the top face, and use the inverter with the output current reduced) / 5 to 95% (free from condensation and vapor). | ||||||||
Protective method / cooling method | IP 20 Enclosed type (IEC60529) / Self-cooling (0.4kW or less of 1-phase 120V input class) | IP20 / Forced air-cooled | |||||||
Built-in filter | 1-phase 240V class: High attenuation EMI filter, 1-phase 120V class and 3-phase 240V class: no filter |