Inverter Fuji Electric Frenic Mini 0.1kW – 2.2kW 1-phase 200V models
- FRN0.1C1S-7A : 0.1kW (1/8HP)
- FRN0.2C1S-7A: 0.2kW (1/4HP)
- FRN0.4C1S-7A : 0.4kW (1/2HP)
- FRN0.75C1S-7A : 0.75kW (1HP)
- FRN1.5C1S-7A : 1.5kW (2HP)
- FRN2.2C1S-7A : 2.2kW (3HP)
EMC filter built-in type
- FRN0.1C1E-7A : 0.1kW (1/8)
- FRN0.2C1E-7A : 0.2kW (1/4HP)
- FRN0.4C1E-7A : 0.4kW (1/2HP)
- FRN0.75C1E-7A : 0.75kW (1HP)
- FRN1.5C1E-7A : 1.5kW (2HP)
- FRN2.2C1E-7A : 2.2kW (3HP)
Features
- High starting torque, at 150% or more
- Trip-free operation
- Stable operation even for a step load
- Braking resistor connectable to the inverter
- Reduce motor instability at low speed
- The highly used functions for and pumps
- Automatic energy-saving provides as a standard functions
- PID control function
- Cooling fan On/Off control function
- Ideal functions to serve a multiplicity of need for small-capacity inverters
- Compatible with a wide range of frequency setting
- The output frequency can be set to a maximum of 400Hz
- A transistor output is provided
- Two point can be set for a non-linear V/f pattern
- Compact
- Simple operation and wiring
- Interface for peripheral devices and comprehensive protective functions
- Flexible through optionals
Specifications
Item |
Specifications |
|||||||
Type |
FRN0.1C1S-7A | FRN0.2C1S-7A | FRN0.4C1S-7A | FRN0.75C1S-4A | FRN1.5C1S-4A | FRN2.2C1S-4A | ||
Applicable motor rating *1 (kW) |
0.1 | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | ||
Output Ratings | Rated capacity *2 (kVA) | 0.3 | 0.57 | 1.1 | 1.9 | 3.0 | 4.1 | |
Rated voltage *3 (V) | Three-phase, 200V/50Hz, 200, 220, 230V/60Hz | |||||||
Rated current *4 (A) | 0.8 (0.7) |
1.5 (1.4) |
3.0 (2.5) |
5.0 (4.2) |
8.0 (7.0) |
11.0 (10.0) |
||
Overload capability | 150% of rated current for 1 min, 200% of rated current for 0.5s | |||||||
Rated frequency | 50, 60Hz | |||||||
Input Rating | Phases, voltage, frequency |
Single-phase, 200 to 240V, 50/60Hz | ||||||
Voltage/frequency variations | Voltage: +10 to -10% Frequency: +5 to -5% | |||||||
Memontary voltage dip capability *5 | When the input voltage is 165V or more, the inverter continues operation. If it drops bellow 165V, the inverter operates for 15ms. | |||||||
Rated current *6 | With DCR | 1.1 | 2.0 | 3.5 | 6.4 | 11.6 | 17.5 | |
Without DCR | 1.8 | 3.3 | 5.4 | 9.7 | 16.4 | 24.8 | ||
Required power supply capacity *7 kVA | 0.3 | 0.4 | 0.7 | 1.3 | 2.4 | 3.5 | ||
Braking | Torque *8 % |
150 | 100 | 50 | 30 | |||
Braking Transistor % | – | 150 | ||||||
DC injection braking | Starting frequency: 0.0 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current | |||||||
Enclosure (IEC 60529) | IP20, UL open type | |||||||
Cooling method | Natural Cooling | Fan Cooling | ||||||
Weight/Mass (kg) | 0.6 | 0.6 | 0.6 | 0.8 | 1.7 | 2.3 |