Inverter Toshiba Tosvert VF-S11
Input Voltage/Capacity range :
- 1 phase 200V 0.2~2.2kW
- 3 phase 200V 0.4~15kW
- 3 phase 400V 0.4~15kW
- 3 phase 600V 0.75~15kW
- 1 phase 200V 0.2~2.2kW (IP54)
- 3 phase 400V 0.75~3.7kW (IP54)
VF-S11 Models
1-phase 240V 0.2~2.2kW models
- VFS11S-2002PL : 0.2kW
- VFS11S-2004PL : 0.4kW
- VFS11S-2007PL : 0.75kW
- VFS11S-2015PL : 1.5kW
- VFS11S-2022PL : 2.2kW
3-phase 240V 0.4~15kW models
- VFS11-2004PM : 0.4kW
- VFS11-2005PM : 0.55kW
- VFS11-2007PM : 0.75kW
- VFS11-2015PM : 1.5kW
- VFS11-2022PM : 2.2kW
- VFS11-2037PM : 4.0kW
- VFS11-2055PM : 5.5kW
- VFS11-2075PM : 7.5kW
- VFS11-2110PM : 11kW
- VFS11-2150PM : 15kW
3-phase 500V 0.4~15kW models
- VFS11-4004PL : 0.4kW
- VFS11-4007PL : 0.75kW
- VFS11-4015PL : 1.5kW
- VFS11-4022PL : 2.2kW
- VFS11-4037PL : 4.0kW
- VFS11-4055PL : 5.5kW
- VFS11-4075PL : 7.5kW
- VFS11-4110PL : 11kW
- VFS11-4150PL : 15kW
3-phase 600V 0.75~15kW models
- VFS11S-6007P : 0.75kW
- VFS11S-6015P : 1.5kW
- VFS11S-6022P : 2.2kW
- VFS11S-6037P : 4.0kW
- VFS11S-6055P : 5.5kW
- VFS11S-6075P : 7.5kW
- VFS11S-6110P : 11kW
- VFS11S-6150P : 15kW
Totally-Enclosed Box Type Inverter: IP54
1-phase 240V class IP54
- VFS11S-2002PLE : 0.2kW
- VFS11S-2004PLE : 0.4kW
- VFS11S-2007PLE : 0.75kW
- VFS11S-2015PLE : 1.5kW
- VFS11S-2022PLE : 2.2kW
3-phase 240V class IP54
- VFS11S-2004PME : 0.4kW
- VFS11S-2007PME : 0.75kW
- VFS11S-2015PME : 1.5kW
- VFS11S-2022PME : 2.2kW
- VFS11S-2037PME : 4.0kW
3-phase 500V class IP54
- VFS11S-4007PLE : 0.75kW
- VFS11S-4015PLE : 1.5kW
- VFS11S-4022PLE : 2.2kW
- VFS11S-4037PLE : 4.0kW
Standard specificaitons
3-phase 240V
Item | Specification | ||||||||||
Input voltage class | 3-phase 240V | ||||||||||
Applicable motor (kW) | 0.4 | 0.55 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | 15 | |
Rating | Type | VFS11- | |||||||||
Form | 2004PM | 2005PM | 2007PM | 2015PM | 2022PM | 2037PM | 2055PM | 2075PM | 2110PM | 2150PM | |
Capacity (kVA) Note 1) | 1.3 | 1.4 | 1.8 | 3.0 | 4.2 | 6.7 | 10 | 13 | 21 | 25 | |
Rated output current (A) Note 2) | 3.3 (3.3) |
3.7 (3.3) |
4.8 (4.4) |
8.0 (7.9) |
11.0 (10.0) |
17.5 (16.4) |
27.5 (25.0) |
33 (33) |
54 (49) |
66 (60) |
|
Output voltage Note 3) | 3-phase 200V to 240V | ||||||||||
Overload current rating | 150%-60 seconds, 200%-0.5 second Note 4) | ||||||||||
Power supply | Voltage-frequency | 3-phase 200V to 240V – 50/60Hz | |||||||||
Allowable fluctuation | Voltage + 10%, -15% Note 5), frequency +/-5% | ||||||||||
Protective method | IP20 Enclosed type (JEM1030) | ||||||||||
Cooling method | Self-cooling | Forced air-cooled | |||||||||
Color | Munsel 5Y-8/0.5 | ||||||||||
Built-in filter | Basic filter Note 7) |
3-phase 500V
Item | Specification | |||||||||
Input voltage class | 3-phase 500V | |||||||||
Applicable motor (kW) | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | 15 | |
Rating | Type | VFS11- | ||||||||
Form | 4004PL | 4007PL | 4015PL | 4022PL | 4037PL | 4055PL | 4075PL | 4110PL | 4150PL | |
Capacity (kVA) Note 1) | 1.1 | 1.8 | 3.1 | 4.2 | 7.2 | 11 | 13 | 21 | 25 | |
Rated output current (A) Note 2) | 1.5 (1.5) |
2.3 (2.1) |
4.1 (3.7) |
5.5 (5.0) |
9.5 (8.6) |
14.3 (13.0) |
17.0 (17.0) |
27.7 (25.0) |
33 (30) |
|
Output voltage Note 3) | 3-phase 380V to 500V | |||||||||
Overload current rating | 150%-60 seconds, 200% -0.5 second Note 4) | |||||||||
Power supply | Voltage-frequency | 3-phase 380V to 500V – 50/60Hz | ||||||||
Allowable fluctuation | Voltage + 10%, -15% Note 5), frequency +/-5% | |||||||||
Protective method | IP20 Enclosed type (JEM1030) | |||||||||
Cooling method | Forced air-cooled | |||||||||
Color | Munsel 5Y-8/0.5 | |||||||||
Built-in filter | High-attenuation EMI filter Note 8) |
1-phase 240V, 3-phase 600V
Item | Specification | |||||||||||||
Input voltage class | 1-phase 240V | 3-phase 600V Note 6) | ||||||||||||
Applicable motor (kW) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | 0.75 | 1.5 | 2.2 | 4.0 | 5.5 | 7.5 | 11 | 15 | |
Rating | Type | VFS11S- | VFS11 | |||||||||||
Form | 2002PL | 2004PL | 2007PL | 2015PL | 2022PL | 6007P | 6015P | 6022P | 6037P | 6055P | 6075P | 6110P | 6150P | |
Capacity (kVA) Note 1) | 0.6 | 1.3 | 1.8 | 3.0 | 4.2 | 1.7 | 2.7 | 3.9 | 6.1 | 9.0 | 11 | 17 | 22 | |
Rated output current (A) Note 2) |
1.5 (1.5) | 3.3 (3.3) | 4.8 (4.4) | 8.0 (7.9) | 11.0 (10.0) | 1.7 (1.5) | 2.7 (2.4) | 3.9 (3.5) | 6.1 (5.5) | 9.0 (8.1) | 11.0 (9.9) | 17.0 (15.3) | 22.0 (19.8) | |
Output voltage Note 3) | 3-phase 200V to 240V | 3-phase 525V to 600V | ||||||||||||
Overload current rating | 150%-60 seconds, 200%-0.5 second Note 4) | 150%-60 seconds, 200%-0.5 second Note 4) | ||||||||||||
Power supply | Voltage-frequency | 1-phase 200V to 240V . 50/60Hz | 3-phase 525V to 600V . 50/60Hz | |||||||||||
Allowable fluctuation | Voltage + 10%, -15% Note 5), frequency+/-5% | Voltage + 10%, -15% Note 5), frequency+/-5% | ||||||||||||
Protective method | IP20 Enclosed type (JEM1030) | IP20 Enclosed type (JEM1030) | ||||||||||||
Cooling method | Self-cooling | Forced air-cooled | Forced air-cooled | |||||||||||
Color | Munsel 5Y-8/0.5 | Munsel 5Y-8/0.5 | ||||||||||||
Built-in filter | High-attenuation EMI filter Note 8) | No filter |
Totally-Enclosed Box Type Inverter: IP54
Item | Specification | |||||||
Input voltage class | 1-phase 240V class/3-phase 240V class/3-phase 500V class | |||||||
Applicable motor (kW) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | 4.0 | ||
Model | Voltage class | Model number | VFS11S/VFS11 | |||||
1-phase 240V class | VFS11S- | 2002PLE | 2004PLE | 2007PLE | 2015PLE | 2022PLE | – | |
3-phase 240V class | VFS11- | – | 2004PME | 2007PME | 2015PME | 2022PME | 2037PME | |
3-phase 500V class | VFS11- | – | – | 4007PLE | 4015PLE | 4022PLE | 4037PLE | |
Rating | Capacity (kVA) | Note 1: | 0.6 | 1.3 | 1.8 | 3.0/3.0/3.1 | 4.2 | 6.7/7.2 |
Output current (A) Note 2: | 1-phase 240V | 1.5 (1.5) | 3.3 (3.3) | 4.8 (4.4) | 8.0 (7.9) | 11.0 (10.0) | – | |
3-phase 240V | – | 3.3 (3.3) | 4.8 (4.4) | 8.0 (7.9) | 11.0 (10.0) | 17.5 (16.4) | ||
3-phase 500V | – | – | 2.3 (2.1) | 4.1 (3.7) | 5.5 (5.0) | 9.5 (8.6) | ||
Output voltage Note 3: | 240V class: 3-phase 200 to 240V, 500V class: 3-phase 380 to 500V | |||||||
Overload current rating | 150%-1min., 200%-0.5 sec. (50%-reduction value) | |||||||
Power supply | Voltage-frequency | 240V class: 1-phase/3-phase 200 to 240V-50/60Hz, 500V class: 3-phase 380 to 500V-50/60Hz | ||||||
Allowable fluctuation | Voltage+10%, -15% Note 4:, Frequency+/-5% | |||||||
Protective method | Totally enclosed type (JEM1030) compliant with IP54/possible to bring into compliance with IP55 Note 5: | |||||||
Cooling method | Self-cooled (with a built-in cooling fan. 1-phase/3-phase 240V-0.75kW or smaller: Cooling fan not provided) | |||||||
Color | Munsel 5Y-8/0.5 | |||||||
Built-in filter | 1-phase & 500V class: High-attenuation EMI filter, 3-phase 240V class: Standard filter | |||||||
Environments | Use environments | Indoor type. Altitude: Not more than 1000m. Place free from corrosive and explosive gases |
||||||
Ambient temperature | -10 to +40 degree | |||||||
Storage temperature | -25 to +70 degree | |||||||
Relative humidity | 20 to 93% | |||||||
Vibration | 5.9m/s2 or less (10 to 55Hz) |