Specifications
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1000/1000 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | -5 to 55 |
Use Area Humidity (%RH) | 10-85 (No condensation) |
External Dimensions (mm) | H1070×W400×D99 |
Volume (kg) | 25 |
Surface Finish | SUS-HL Finish |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 3.2 / 3.0 |
Consumption Current/MAX (A) | 4.2 / 4.0 |
Consumption Voltage/Rating (W) | 500 |
Consumption Voltage/MAX (W) | 600 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | IPX4 (ENC-SUS unit only) Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFO-1234yf 350g |
Noise (dB) | 78 |
External Output | Alarm output (No-voltage/normal open: resistive load 250V 2A) Can be switched to no-voltage/normal close by setting |
Display | Internal temperature / Error / RUN |
Environmental Response | RoHS |