Power Supply Unit CJ-series

Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance. Lineup of five models including the AC power supply (25W).

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Compare
Category: PLC Controller
Share
Facebook
Twitter
Google
Email
Pinterest
  • Description
  • Additional information
  • About brand
  • Order Information
Description

CJ1W-PA/PD

Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance. Lineup of five models including the AC power supply (25W).

The replacement notification function can prevent an overflow of the system due to the power lifetime. (CJ1W-PA205C only)

Power Supply Unit provides wide variations according to the system scale up to maximum 25 W.

Power Supply Unit provides wide variations according to the power supply (100 to 240 V AC/ 24 V DC) status.

The output contact during operation enables you to check the CPU operation. (CJ1W-PA205R only)

Conforming to the SEMI-F47 Standard. *

*AC input type, 200 V min. input.

Specifications :

Item Specifications
Model CJ1W-PA205R CJ1W-PA205C CJ1W-PA202
Supply voltage 100 to 240 V AC (wide-range), 50/60 Hz
Operating voltage and
frequency ranges
85 to 264 V AC, 47 to 63 Hz
Power consumption 100 VA max. 50 VA max.
Inrush current *1 At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperature
At 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature
At 100 to 120 V AC:
20 A/8 ms max. for cold start at
room temperature
At 200 to 240 V AC:
40 A/8 ms max. for cold start at
room temperature
Output capacity *7 5.0 A, 5 V DC (including supply to CPU Unit) 2.8 A, 5 V DC
(including supply to CPU Unit)
0.8 A, 24 V DC 0.4 A, 24 V DC
Total: 25 W max. Total: 14 W max.
Output terminal
(service supply)
Not provided.
RUN output *2 Contact configuration: SPST-NO
Switch capacity:
250 V AC, 2 A (resistive load)
120 V AC, 0.5 A (inductive load),
24 V DC, 2A (resistive load)
24 V DC, 2 A (inductive load)
Not provided.
Replacement
notification function
Not provided. With Alarm output (open-collector
output)
30 V DC max., 50 mA max.
Not provided.
Insulation resistance 20 MΩ min. (at 500 V DC) between
AC external and GR terminals *3
20 MΩ min. (at 500 V DC) between
all external terminals and GR
terminal *3, and between all alarm
output terminals.
20 MΩ 1 min. (at 250 V DC)
between all alarm output terminals
and GR terminal *3.
20 MΩ min. (at 500 V DC) between
AC external and GR terminals *3
Dielectric strength *4 2,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
2,300 VAC, 50/60 Hz for 1 min
between all external terminals and
GR terminal *3 and between all
alarm output terminals with a
leakage current of 10 mA max.
1,000 V AC, 50/60 Hz for 1 min
between all alarm output terminals
and GR terminal *3 with a leakage
current of 10 mA max.
2,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
1,000 V AC, 50/60 Hz for 1 minute between DC external and GR terminals *3
Leakage current: 10 mA max.
Noise immunity 2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance Conforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistance Conforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operating
temperature
0 to 55 ° C
Ambient operating
humidity
10% to 90% (with no condensation) 10% to 90% (with no condensation) *5 10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gases.
Ambient storage
temperature
– 20 to 70 ° C (excluding battery) – 20 to 75 ° C *5 – 20 to 75 ° C (excluding battery)
Grounding Less than 100 Ω
Enclosure Mounted in a panel.
Weight All models are each 5 kg max.
CPU Rack dimensions 90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note:
W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31; CJ1M-CPU2[] = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units
or I/O Control Units and m is the number of other Units.
Safety measures Conforms to cULus and EC Directives.

 

Item
Power Supply Unit
Specifications
CJ1W-PD025 CJ1W-PD022
Supply voltage 24 VDC
Operating voltage and
frequency ranges
19.2 to 28.8 V DC 21.6 to 26.4 V DC
Power consumption 50 W max. 35 W max.
Inrush current *1 At 24 V DC: 30 A/20 ms max. for cold start
Output capacity *7 5.0 A, 5 V DC (including supply to CPU Unit) 2.0 A, 5 V DC (including supply to CPU Unit)
0.8 A, 24 V DC 0.4 A, 24 V DC
Total: 25 W max. Total: 19.6 W max.
Output terminal
(service supply)
Not provided.
RUN output *2 Not provided.
Replacement
notification function
Not provided.
Insulation resistance 20 MΩ min. (at 500 V DC) between DC external
and GR terminals *3
—
*6
Dielectric strength *4 1,000 V AC, 50/60 Hz for 1 min between DC
external and GR terminals *3
Leakage current: 10 mA max.
—
*6
Noise immunity 2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance Conforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min)
Shock resistance Conforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operating
temperature
0 to 55 ° C
Ambient operating
humidity
10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gases.
Ambient storage
temperature
– 20 to 75 ° C (excluding battery)
Grounding Less than 100 Ω
Enclosure Mounted in a panel.
Weight All models are each 5 kg max.
CPU Rack dimensions 90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note:
W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31; CJ1M-CPU2[] = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units
or I/O Control Units and m is the number of other Units.
Safety measures Conforms to cULus and EC Directives.

*1.Disconnect the Power Supply Units LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit.

*2.Supported only when mounted to CPU Rack.

*3.The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element with a low-temperature current control characteristic. If the ambient temperature is high or the PLC is hot-started, the thermistor will not be sufficiently cool, and the inrush currents given in the table may be exceeded by up to twice the given values. When selecting fuses or breakers for external circuits, allow sufficient margin in shut-off performance.

*4.Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for longer than 3 months to keep the replacement notification function in optimum working condition.

*5.Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.

*6.CJ1W-PD022 is not insulated between the primary DC power and secondary DC power.

*7.Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an extended period of time exceeding the power supply output capacity or if the outputs are shorted.

Checking Current Consumption and Power Consumption

After selecting a Power Supply Unit based on considerations such as the power supply voltage, calculate the current and power requirements for each Rack.

Condition 1: Current Requirements

There are two voltage groups for internal power consumption: 5 V and 24 V.
Current consumption at 5 V (internal logic power supply)
Current consumption at 24 V (relay driving power supply)

Condition 2: Power Requirements

For each Rack, the upper limits are determined for the current and power that can be provided to the mounted Units. Design the system so that the total current consumption for all the mounted Units does not exceed the maximum total power or the maximum current supplied for the voltage groups shown in the following tables.
The maximum current and total power supplied for CPU Racks and Expansion Racks according to the Power Supply Unit model are shown below.

Note:

1.For CPU Racks, include the CPU Unit current and power consumption in the calculations. When expanding, also include the current and power consumption of the I/O Control Unit in the calculations.

2.For Expansion Racks, include the I/O Interface Unit current and power consumption in the calculations.

Power Supply Units Max. current supplied Max. total power supplied
5 V 24 V (relay driving current)
CJ1W-PA205R 5.0 A 0.8 A 25 W
CJ1W-PA205C 5.0 A 0.8 A 25 W
CJ1W-PA202 2.8 A 0.4 A 14 W
CJ1W-PD025 5.0 A 0.8 A 25 W
CJ1W-PD022 2.0 A 0.4 A 19.6 W

Conditions 1 and 2 below must be satisfied.

Condition 1: Maximum Current

(1)Total Unit current consumption at 5 V ≤ (A) value
(2)Total Unit current consumption at 24 V ≤ (B) value

Condition 2: Maximum Power

(1) × 5 V + (2) × 24 V ≤ (C) value

Example: Calculating Total Current and Power Consumption

Example: When the Following Units are Mounted to a CJ-series CPU Rack Using a CJ1W-PA202 Power Supply Unit

Unit type Model Quantity Voltage group
5 V 24 V
CPU Unit CJ1G-CPU45H 1 0.910 A —
I/O Control Unit CJ1W-IC101 1 0.020 A —
Basic I/O Units
(Input Units)
CJ1W-ID211 2 0.080 A —
CJ1W-ID231 2 0.090 A —
Basic I/O Units
(Output Units)
CJ1W-OC201 2 0.090 A 0.048 A
Special I/O Unit CJ1W-DA041 1 0.120 A —
CPU Bus Unit CJ1W-CLK23 1 0.350 A —
Current consumption Total 0.910 + 0.020 + 0.080 × 2 + 0.090 ×
2 + 0.090 × 2 + 0.120 + 0.350
0.048 A × 2
Result 1.92 A ( ≤ 2.8 A) 0.096 A ( ≤ 0.4 A)
Power consumption Total 1.92 × 5 V = 9.60 W 0.096 A × 24 V = 2.304 W
Result 9.60 + 2.304 Power_Supply_Unit_CJ-series.jpg 11.904 W ( ≤ 14 W)
Additional information
Brand

Mitsubishi Electric

About brand

Mitsubishi Electric Corporation (三菱電機株式会社 Mitsubishi Denki Kabushiki-gaisha) is a Japanese multinational electronics and electrical equipment manufacturing company headquartered in Tokyo, Japan. It is one of the core companies of Mitsubishi. Mitsubishi Electric manufactures electric and architectural equipment, and is a major worldwide producer of photovoltaic panels.[5] The corporation was established on 15 January 1921. In the United States, products are manufactured and sold by Mitsubishi Electric United States headquartered in Cypress, California

distributor mitsubishi indonesia,mitsubishi indonesia,repair inverter mitsubishi,plc mitsubishi,mitsubishi drive,servo mitsubishi,mitsubishi plc
MORE PRODUCTS

Analog I/O Melsec-Q Series

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Base Unit Melsec iQ-R PLC Mitsubishi

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

CPU Melsec iQ-R PLC Mitsubishi

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

FR-A741 Frequency Inverters Mitsubishi

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

FR-A800 Frequency Inverters Mitsubishi

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

FR-A820 Frequency Inverters 240V

Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close
Order Information

SEND US AN EMAIL

CONTACT US

icons8-phone-64
Phone: +62-21 8080 8846
icons8-touchscreen-96
Mobile: +62-822 600 600 63
icons8-new-post-64
Email: iqbal@pinanggih.co.id,sales@pinanggih.co.id
icons8-office-phone-64
Fax: +62-21 8080 8847
icons8-map-marker-96
Address: D'MANSION Blok A20 Business Park Jl Dr.Krt Radjiman Wijodiningrat Jatinegara Indah, Pulo Gdung, Jakarta

Do you have questions about how we can help your company?
Send us an email and we’ll get in touch shortly.

Related products

Close

Mitsubishi PLC Q Series tipe Q25PRHCPU

Mitsubishi PLC Q Series tipe Q25PRHCPU

PLC Tipe Q25PRHCPU ini adalah Mitsubishi PLC System Q (Q Series) merupakan Modular PLC system
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

PLC Battery CR17335SE-MC

Spesifikasi PLC Battery CR17335SE-MC
  • Chrome Battery PLC Controller Battery for CR17335SE-MC Mitsubishi Q6BAT
  • 0.68in (length), 0.68in (width), 1.34in (height); 1.00lbs
  • High Energy Lithium Cells
  • Stable Voltage
  • Broad Temperature Range
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Mitsubishi Compact PLC Melsec FX1N

Mitsubishi Compact PLC Melsec FX1N menggabungkan manfaat dari kontroler kompak dengan kemampuan ekspansi yang fleksibel dari sistem kontrol modular. Hal ini dapat diperluas hingga 128 input dan output dan dengan berbagai komprehensif modul fungsi khusus.
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

MELSEC WS Safety Controller

The MELSEC WS Safety Controller provides a cost effective way to add a safety controller capability to individual machines, or smaller scale systems.
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Mitsubishi Compact PLC Melsec FX1S

Controller dari seri Mitsubishi Compact PLC Melsec FX1S series memberikan fungsi yang luar biasa sampai dengan I/O 30  dalam paket yang sangat kompak. Mitsubishi Compact PLC Melsec FX1S series sangat ideal untuk aplikasi sulit untuk akses instalasi dan sistem di mana pelayanan yang normal tidak mungkin
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Mitsubishi PLC FX1S-30M

PLC has been widely used in domestic and foreign iron and steel, petroleum, chemical, power, building materials, machinery manufacturing, automobile, textile, transportation, environmental protection and cultural entertainment and other industries
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Mitsubishi PLC A171SHCPUN

PLC has been widely used in domestic and foreign iron and steel, petroleum, chemical, power, building materials, machinery manufacturing, automobile, textile, transportation, environmental protection and cultural entertainment and other industries
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Close

Mitsubishi PLC Q Series tipe Q12PHCPU

Mitsubishi PLC Q Series tipe Q12PHCPU

PLC Tipe Q12PHCPU ini adalah Mitsubishi PLC System Q (Q Series) merupakan Modular PLC system
Add to Wishlist loading
Product added! Browse Wishlist
The product is already in the wishlist! Browse Wishlist
Quick View
Yokogawa
Yaskawa
Yamatake
WEG
Toshiba
Terasaki
Teco
Sumitomo Technologies
Siemens
Schneider
Rittal
Pro Face
Panasonic
Omron
MKCells
Mitsubishi Electric
Idec
ICP DAS
Fuji ELectric
Franklin
© 2021 PT Pinanggih Teknikatama. All rights reserved.Maknative Konsultan Pajak Rumah Kayu jasa konsultan pajak Sewa Truk Mobil Golf
close
Start typing to see products you are looking for.
  • Home
  • About
    • About
    • Service Business
  • Products
  • Experience
  • Career
  • Contact
  • Article
Scroll To Top