Wide Model Variation
Basic Type
Suitable for the equipment that uses a peripheral device to suppress noise or harmonics
EMC filter built-in type
By adopting built-in filter, this type is compliant with European EMC Directives category C3 (2nd Env) ‘EN61800-3-2004’.
Frenic Mega 75kW to 630kW 400V 3-phase
- FRN75G1E-4A (75kW 400V 3 phase)
- FRN90G1E-4A (90kW 400V 3 phase)
- FRN110G1E-4A (110kW 400V 3 phase)
- FRN132G1E-4A (132kW 400V 3 phase)
- FRN160G1E-4A (160kW 400V 3 phase)
- FRN200G1E-4A (200kW 400V 3 phase)
- FRN220G1E-4A (220kW 400V 3 phase)
- FRN280G1E-4A (280kW 400V 3 phase)
- FRN315G1E-4A (315kW 400V 3 phase)
- FRN355G1E-4A (355kW 400V 3 phase)
- FRN400G1E-4A (400kW 400V 3 phase)
- FRN500G1E-4A (500kW 400V 3 phase)
- FRN630G1E-4A (630kW 400V 3 phase)
75kW to 630kW High Duty specification for heavy load
Item
|
Specifications
|
||||||||||||||
Type (FRN□□□G1E-4□) | 75 | 90 | 110 | 132 | 160 | 200 | 220 | 280 | 315 | 355 | 400 | 500 | 630 | ||
Nominal applied motor [kW] (*1) | 75 | 90 | 110 | 132 | 160 | 200 | 220 | 280 | 315 | 355 | 400 | 500 | 630 | ||
Output ratings | Rated capacity [kVA] (*2) | 114 | 134 | 160 | 192 | 231 | 287 | 316 | 396 | 445 | 495 | 563 | 731 | 891 | |
Rated voltage [V] (*3) |
Three-phase 380 to 480V (with AVR)
|
||||||||||||||
Rated Current [A] | 150 | 176 | 210 | 253 | 304 | 377 | 415 | 520 | 585 | 650 | 740 | 960 | 1170 | ||
Overload capability |
150% for 1min, 200% for 3.0s
|
||||||||||||||
Rated frequency [Hz] |
50, 60Hz
|
||||||||||||||
Input ratings | Main circuit power Phases, voltage, frequency |
Three-phase 380 to 440V/50Hz
Three-phase 380 to 480V/60Hz |
|||||||||||||
Auxiliary control power input Phases, voltage, frequency |
Single-phase 380 to 480V, 50/60Hz
|
||||||||||||||
Auxiliary power input for fan Phases, voltage, frequency (*5) |
Single-phase 380 to 440V/50Hz
Single-phase 380 to 480V/60Hz |
||||||||||||||
Voltage, frequency variations |
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5%
|
||||||||||||||
Rated current [A] (*7) | with DCR | 138 | 164 | 201 | 238 | 286 | 357 | 390 | 500 | 559 | 628 | 705 | 881 | 1115 | |
without DCR |
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
||
Required power supply capacity [kVA] (*8) | with DCR | 96 | 114 | 140 | 165 | 199 | 248 | 271 | 347 | 388 | 436 | 489 | 611 | 773 | |
Braking | Torque [%] (*9) |
10 to 15%
|
|||||||||||||
Braking transistor |
–
|
||||||||||||||
Min. ohmic value [Ω] Torque [%] |
–
|
||||||||||||||
DC injection braking | Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 100% | ||||||||||||||
EMC filter |
EMC standard compliance: Category C3 is only emission and 2nd Env. is immunity. (EN61800-3:2004)
|
||||||||||||||
DC reactor (DCR) (*10) | Standard accessory | ||||||||||||||
Applicable safety standards |
UL508C, C22.2No.14 (pending), EN61800-5-1:2003
|
||||||||||||||
Enclosure (IEC60529) |
IP00 open type, UL open type
|
||||||||||||||
Cooling method |
Fan cooling
|
||||||||||||||
Weight/Mass [kg] |
43
|