Optimum Exclusive Design for Passenger Elevators
- A braking circuit is built in the inverters of all the capacities
- Built-in PG feedback circuit is standard equipment.
- An optional keypad is available
Higher Performance
- Overload capacity : 200% for 10s
- Current response : 5 times greater than previous models (corporated with the G11UD series
- Reduction of torque ripple realizes low vibration
- Reduced roll-back during starting up
High performance vector control
- Current response (ACR) : 500Hz
- Speed control accuracy : ±0.01%
High overload capacity
- 200% of rated current for 10s (overload begins from 80% continous operation with a carrier frequency of 10kHz).
FRN2.2LM1S-7EA Specifications
Models |
Specifications | |||
Type FRN2.2LM1S-7EAkW (*9) |
2.2 | |||
Nominal applied motor [kW] (*1) | 2.2 | |||
Output ratings | Rated capacity [kVA] (*2) | 4.1 | ||
Rated voltage [V] (*3) | Three-phase 200V-220V, 50/60Hz | |||
Rated current [A] (*4) | 11 | |||
Overload capacity [A] (Permisable energizing time) |
22 (3s) | |||
Rated frequency [Hz] | 50, 60Hz | |||
Input rating | Nominal operation | Main power supply Phases, Voltage, Frequency |
Single-phase, 200 to 240V, 50/60Hz | |
Auxiliary control power input Phases, Voltage, Frequency |
Single-phase, 200 to 240V, 50/60Hz | |||
Voltage/frequency variations (*7) | Voltage: +10 to -15%, Frequency: +5 to -5% | |||
Rated current [A] (*s) | With DCR | 17.5 | ||
Without DCR | 24 | |||
Required power supply capacity [kVA] (*6) | 3.5 | |||
Battery Operation | Main power supply | DC 24V or more in the direct current voltage conversion | ||
Auxillary Control power input (*10) |
Phases, Voltage, Frequency | Single-phase 200 to 240V, 50/60Hz | ||
Voltage/frequency variations | Voltage : +10 to -15%, Frequency: +5 to -5% | |||
Operation time [s] (*11) | 180 | |||
Braking | Braking time [s] (*12) | 60 | ||
Braking duty-cycle (%ED) [%] (*12) | 50 | |||
Rated regenerative power [kW] (*12) | 1.78 | |||
Minimum resistance which can be connected [Ω] (*8) | 33 | |||
DC Reactore (DCR) | Option | |||
Applicable safety standard | EN61800-5-, EN954-1 Category3 | |||
Enclosure (IEC60529) | IP20 | |||
Cooling method | Fan cooling | |||
Weight/Mass [kg] | 3.0 |
(*1) Fuji’s 4-pole standard motor
(*2) Rated capacity is calculated by regarding the output rated voltage as 220V
(*3) Output voltage cannot exceed the power supply voltage
(*4) It is a value in the confition of the career frequency 10kHz and the ambient temperature 45°C.
Selected the inverter capacity such that the square average current in cycle operation is 80% or less of the rated current of an inverter
(*5) The power supply capacity is 500kVA (ten times the inverter capacity when the inverter capacity exceed 50kVA), and the calculation value when connecting with the power supply of %X=5%
(*6) Obtained when a DC Reactor is used
(*7) An acceptable variation of the main power supply and the control power supply assistance input
(*8) The admissible error of minimum resistance is ±5%.
(*9) Type list:
FRN2.2LM1S-7EA : CAN version
FRN2.2LM1S-&EA : DCP version
(*10) The same AC power as the main power supply input is connected for the backup of the control circuit power source
(*11) It is a value in the condition of the career frequency 10kHz and the ambient temperature 455°C.
Use the inverter such that the square average current in battery operation is 80% or less of the rated current of an inverter.
(*12) Braking time and duty cyclw (%ED) are defined by cycle operation at the rated regenerative power as shown in the figure bellow