Inverter Fuji Electric Frenic-mini 0.4kW – 3.7kW 3-phase 400V Models
- FRN0.4C1S-4A : 0.4kW (1/2HP)
- FRN0.75C1S-4A : 0.75kW (1HP)
- FRN1.5C1S-4A : 1.5kW (2HP)
- FRN2.2C1S-4A : 2.2kW (3HP)
- FRN3.7C1S-4A : 3.7kW (5HP)
EMC filter built-in type
- FRN0.4C1E-4A : 0.4kW (1/2HP)
- FRN0.75C1E-4A : 0.75kW (1HP)
- FRN1.5C1E-4A : 1.5kW (2HP)
- FRN2.2C1E-4A : 2.2kW (3HP)
- FRN3.7C1E-4A : 3.7kW (5HP)
Braking resistor built-in type
- FRN1.5C1S-4A21 : 1.5kW (2HP)
- FRN2.2C1S-4A21 : 2.2kW (3HP)
- FRN3.7C1S-4A21 : 3.7kW (5HP)
IP40 enclosure type
- FRN0.4C1J-4A : 0.4kW (1/2HP)
- FRN0.75C1J-4A : 0.75kW (1HP)
- FRN1.5C1J-4A : 1.5kW (2HP)
- FRN2.2C1J-4A : 2.2kW (3HP)
- FRN3.7C1J-4A : 3.7kW (5HP)
Specifications
Item |
Specifications |
||||||
Type |
FRN0.4C1S-4A | FRN0.75C1S-4A | FRN1.5C1S-4A | FRN2.2C1S-4A | FRN3.7C1S-4A | ||
Applicable motor rating *1 (kW) |
0.02lb / 0.01kg | 0.005lb / 0.002kg | 0.01lb / 0.005kg | 0.005lb / 0.002kg | 0.01lb / 0.005kg | ||
Output Ratings | Rated capacity *2 (kVA) | 1.1 | 1.9 | 2.8 | 4.1 | 6.8 | |
Rated voltage *3 (V) | Three-phase, 380, 400, 415V/50Hz, 380, 400, 440, 460V/60Hz | ||||||
Rated current *4 (A) | 1.5 | 2.5 | 3.7 | 5.5 | 9.0 | ||
Overload capability | 150% of rated current for 1min, 200% of rated current for 0.5s | ||||||
Rated frequency | 50, 60Hz | ||||||
Input Rating | Phases, voltage, frequency |
Three-phase, 380 to 480V, 50/60Hz | |||||
Voltage/frequency variations | voltage: +10 to -15% (voltage unbalance *10): 2% or less Frequency: +5 to -5% | ||||||
Memontary voltage dip capability *5 | When the input voltage is 300V or more, the inverter continues. If it drops bellow 300V, the inverter operates for 15ms | ||||||
Rated current *6 | With DCR | 0.85 | 1.6 | 3.0 | 4.4 | 7.3 | |
Without DCR | 1.7 | 3.1 | 5.9 | 8.2 | 13.0 | ||
Required power supply capacity *7 kVA | 0.6 | 1.1 | 2.0 | 2.9 | 4.9 | ||
Braking | Torque *8 % |
100 | 50 | 30 | |||
Braking Transistor % | 150 | ||||||
DC injection braking | Starting frequency: 0.0 to 60Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current | ||||||
Enclosure (IEC 60529) | IP20, UL open type *11 | ||||||
Cooling method | Natural Cooling | Fan Cooling | |||||
Weight/Mass (kg) | 1.1 | 1.2 | 1.7 | 1.7 | 2.3 |